Up to 16 relay outputs, which are freely programmable for switching 3-phase capacitors. Current Measurement: Selectable through connection terminals. Sensitivity: depending on the setting. Dimensions: for panel mounting, with a door cutout requirement of Key Features and Functionality
Includes isolated RS232 and RS485 interfaces for data downloading or GSM connectivity via a dedicated modem. Programming and Operation
The BR 5016 features a menu-driven interface with soft-touch keys for easy navigation. --- Epcos Power Factor Controller Br 5016 Manual Pdf
Users can edit general settings, step settings, and communication parameters through the "Program" key.
The backlit 16 x 2 line LCD display provides real-time data on grid parameters, including voltage ( ), current ( ), frequency ( ), active power ( ), reactive power ( ), and apparent power ( Up to 16 relay outputs, which are freely
The controller's discharge time setting must match the discharge device of the capacitors. Standard Epcos resistors typically require 60 seconds; setting a shorter time can lead to high inrush currents, potential capacitor bursting, or fire. Terminal Configuration: Rear Side: Terminals for voltage and current measurements.
Capable of automatic synchronization to simplify the commissioning process. Installation and Wiring Guidelines Dimensions: for panel mounting, with a door cutout
Proper installation is critical for the safety and longevity of the controller and the associated capacitor banks.
Settings can be secured with a programmable password to prevent unauthorized changes. Target Cos-Phi: The target power factor is adjustable from
Current transformers must be installed such that the load current flows through them. The compensation network outputs must be installed behind the CT in the direction of current flow.