Jte Inverter Manual Now

Connect exclusively to the P+ and PB terminals.

Proper wiring is vital for operational stability. Always disconnect input power before starting work. Standard Specifications (Typical 380V Models) AC 380V 3-phase (-15% to +10%) or 220V single-phase MPPT Range 450VDC–750VDC for 380VAC models Output Frequency 0–50Hz/60Hz Overload Capacity 150% for 1 minute; 180% for 10 seconds Key Wiring Rules: Jte Inverter Manual

Maintain an ambient temperature between -10°C and 50°C. For altitudes above 1,000 meters, derate the output current by 1% for every 100 meters. Connect exclusively to the P+ and PB terminals

Never connect power cables to output terminals (U, V, W). Before mounting the device, ensure the environment meets

Before mounting the device, ensure the environment meets these critical standards to prevent equipment damage or fire risks:

Use MI1/MI2 for digital forward/reverse signals and AI1/AI2 for external potentiometer speed control. 3. Basic Programming and Operation

Mount the unit vertically with at least 150mm of clearance above/below and 50mm on the sides for heat dissipation.